Foutcode Beschrijving Oplossing Ernst
C5 System Configuration C5 1) No jumper cap inserted on the control board Malfunction 2) Incorrect or damaged jumper cap on control board -
E1 System High Pressure E1 1) Over charged with refrigerant 2) Blocked or dirty outdoor coil -
E2 Indoor Anti-Freeze Protection E2 3 flashes 1) Low return airflow and 1 sec Off 2) Indoor fan speed is too low -
E3 Low Pressure Protection E3 9 flashes 1) Low on refrigerant and 1 sec Off 2) Pressure sensor is damaged -
E4 Compressor High Discharge E4 7 flashes Please refer to the malfunction analysis (discharge Temperature Protection and 1 sec Off temperature, overload) in service manual -
E5 Overcurrent Protection E5 5 flashes 1) Supply voltage is unstable and 1 sec Off 2) Supply voltage is too low and system load is too high -
E6 Communication Malfunction E6 Continuous 1) Communication cable is mis-wired between indoor On and outdoor units -
E7 Mode conflict (Indoor units E7 Operation status calling for simultaneously -
E8 High Temperature E8 6 flashes 1) Incorrect refrigerant charge level Resistant Protection and 1 sec Off 2) Refrigerant metering device malfunction -
E9 Cold Air Protection E9 1) Indoor coil has not reach minimum heating temperature 2) Indoor ambient is abnormally cold -
F0 Refrigerant Leakage Protection F0 9 flashes 1) refrigerant leak(s) and 1 sec Off 2) Indoor coil temperature sensor no calibrated -
F1 Indoor Ambient Temperature F1 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor ambient temperature sensor damaged -
F2 Indoor Coil Temperature F2 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor coil temperature sensor damaged -
F3 Outdoor Ambient Temperature F3 6 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor ambient temperature sensor damaged -
F4 Outdoor Coil Temperature F4 5 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor coil temperature sensor damaged -
F5 Outdoor Discharge Temperature F5 7 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Discharge temperature sensor damaged -
F6 Compressor Overload Protection - F6 3 flashes 1) Incorrect refrigerant charge Frequency Decrease/Limit Mode and 1 sec Off 2) Metering device malfunction -
F7 Oil Return Protection - Frequency F7 Normal function status code only Decrease/Limit Mode -
F8 System Current Overload Protection - F8 1 flashes 1) Input voltage too low Frequency Decrease/Limit Mode and 1 sec Off 2) System pressure too low -
F9 High Compressor Discharge F9 2 flashes and 4 flashes 1) Cooling load is too great Temperature - Frequency 1 sec Off and 1 sec Off 2) Outdoor ambient temperature too high -
H1 Defrost Mode in Heating H1 Operation status Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose -
H3 Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose and 1 sec Off 2) Refer to the malfunction analysis in Service Manual -
H5 IPM Module Protection H5 4 flashes 1) IPM module over heating and 1 sec Off 2) Improper or Low voltage at the IPM module -
H6 Indoor DC Fan Motor H6 1) Loose connections between fan motor and control board Malfunction 2) Fan motor or blower wheel bearings malfunction -
H7 Compressor De-Synchronized H7 1) Compressor voltage is not balance Malfunction 2) Control board malfunction -
L1 High DC Bus Voltage Protection PH 13 flashes 1) Supply voltage on L1 and N is above 265Vac and 1 sec Off 2) Capacitor on control board malfunction -
L9 High Input Power Protection L9 9 flashes 1) Compressor malfunction and 1 sec Off 2) Power circuit malfunction -
P5 Compressor Phase Current P5 1) IPM module malfunction Protection 2) Outdoor control board malfunction -
P7 Module Temperature Sensor P7 Outdoor control board malfunction Malfunction -
P8 Module Temperature Protection P8 1) Lack of thermal grease on IPM module 2) Heat sink (radiator) not tightly mounted -
U1 Compressor Phase-Current U1 Outdoor control board malfunction Detection Malfunction -
U3 DC Bus Voltage Dip U3 Outdoor control board malfunction Input Current Detection Malfunction U5 Outdoor control board malfunction -
U5 Input Current Detection Malfunction U5 Outdoor control board malfunction The four-way valve is abnormal U7 Hardware malfunction -
U7 The four-way valve is abnormal U7 Hardware malfunction Zero cross detection circuit U8 Hardware malfunction -
U8 Zero cross detection circuit U8 Hardware malfunction malfunction(for indoor unit) -