Probleemoplossing - CyberPower SM120KMF

Veelvoorkomende problemen en oplossingen - ook zonder foutcode op het display.

16 van 16

Overige problemen 9

Probleem Oorzaak Oplossing

Stroomvoorziening & Elektronica 7

Probleem Oorzaak Oplossing
Utility (Grid) is abnormal Mains voltage or frequency exceeds the upper or lower limit Check the input phase voltage of rectifier
Bypass Sequence Error Bypass voltage sequence is reverse Check if input power cables are connected correctly
Bypass Voltage Abnormal Amplitude or frequency of bypass voltage exceeds the limit Check if relevant alarms exist (bypass circuit breaker open, Bypass Sequence Error, IP Neutral Lost). Verify bypass voltage and frequency are within setting range. If abnormal, measure actual bypass voltage and frequency, check external bypass power supply. Increase bypass high limit set point if alarm occurs frequently
Bypass Over Load Bypass current is over the limitation (above 135% of the rated current) Reduce the load or check bypass circuit
Bypass Freq. Over Track Frequency of bypass voltage exceeds the limit Check if relevant alarms exist (bypass circuit breaker open, Bypass Sequence Error, IP Neutral Lost). Verify bypass frequency is within setting range. Measure actual bypass frequency, check external bypass power supply. Increase bypass high limit set point if alarm occurs frequently

Community-vragen

Stel een vraag

Was ist 3 + 4?
De foutcodes zijn afkomstig uit de officiële handleiding van de fabrikant. Bezoek de officiële CyberPower website voor actuele informatie en ondersteuning.

Andere CyberPower producten

Foutcode-assistent Online
Hallo! Ik ben uw foutcode-assistent voor de CyberPower SM120KMF. Voer een foutcode in en ik leg u uit wat het betekent en hoe u het probleem kunt oplossen.